UT_SETTING_CHECK — Check a setting before it is used
UT_SETTING_CHECK — Check a setting before it is used
An HMI or SCADA user can type anything: a stop level above the start level, a
negative time, a number with a slipped decimal point. UT_SETTING_CHECK takes a
written setting only if it is sensible, and otherwise keeps the old one and says
why, as a UT_FAULT code the HMI turns into its own words (not below related).
UT_SETTING_ARRAY does the same for a whole list of settings in one block (see
below).
Pins (UT_SETTING_CHECK)
| Pin | Type | Default | What to wire | |
|---|---|---|---|---|
| in | New |
REAL | 0.0 | The value the master wrote: its own variable, not the setting in use |
| in | Written |
BOOL | FALSE | Rising edge: check New now, even if unchanged (an HMI "Apply" button) |
| in | MinValue |
REAL | −3.4E38 | Lowest value allowed (allowed itself) |
| in | MaxValue |
REAL | 3.4E38 | Highest value allowed (allowed itself) |
| in | Above |
REAL | −3.4E38 | Must be above this related setting (H above L). Unwired: no check |
| in | Below |
REAL | 3.4E38 | Must be below this related setting (L below H). Unwired: no check |
| out | Accepted |
BOOL | One scan: New was taken into Value |
|
| out | Refused |
BOOL | One scan: New was refused, Value kept |
|
| out | Bad |
BOOL | Value itself fails the checks now (written past this block, or a limit or related setting has moved since) |
|
| out | RefusedWhy |
UT_FAULT | Why the last write was refused (below); UT_F_NONE after an accepted one |
|
| inout | Value |
REAL | The setting in use (in your settings record) |
How it works
New is checked each time it changes, or on a rising edge of Written:
| Check | RefusedWhy when it fails |
Words (as in UT_STATUS_TEXT) |
|---|---|---|
| Not NaN, not infinite | UT_F_VALUE_BAD |
value not a number |
The limits are numbers, and MinValue ≤ MaxValue |
UT_F_LIMITS |
limits not valid |
New ≥ MinValue |
UT_F_BELOW_MIN |
below minimum |
New ≤ MaxValue |
UT_F_ABOVE_MAX |
above maximum |
New > Above (strictly: equal is refused) |
UT_F_NOT_ABOVE |
not above related |
New < Below (strictly) |
UT_F_NOT_BELOW |
not below related |
Passed: Value := New, RefusedWhy UT_F_NONE. Refused: Value keeps its old value
and RefusedWhy says why. The HMI knows which setting it wrote, so it can show its
own words, e.g. "L refused: not below H".
- A master that writes the same refused value every poll is refused once (the value
hasn't changed). After fixing the related setting, write the value again, or
pulseWritten. - Nothing is checked on the first scan after a power cut or PLC start:
Newis
only read. A master variable that comes back 0 never overwrites a setting kept in
aRETAINrecord. - The HMI shows
Value(the setting in use) and writesNew. - For two related settings use two blocks, each with the other as its limit:
L withBelow := H, H withAbove := L.
LChk(New := HMI_LevelL, MinValue := 0.0, MaxValue := 5.0, Below := Cfg.levelH,
Value := Cfg.levelL);
HChk(New := HMI_LevelH, MinValue := 0.0, MaxValue := 5.0, Above := Cfg.levelL,
Value := Cfg.levelH);
HRefused := HChk.RefusedWhy; (* UT_F_NOT_ABOVE: H not above L *)
UT_SETTING_ARRAY — a list of settings
| Pin | Type | Default | What to wire | |
|---|---|---|---|---|
| out | Accepted |
BOOL | One scan: a request was taken | |
| out | Refused |
BOOL | One scan: a request was refused | |
| out | AnyBad |
BOOL | An item's value fails its checks now |
|
| out | RefusedItem |
INT | Position of the last refused item (1 = the first element; 0 = none since power-up) | |
| out | RefusedWhy |
UT_FAULT | Why it was refused (as UT_SETTING_CHECK's); kept until the next refusal | |
| inout | Items |
ARRAY[*] OF UT_SETTING | The settings, any size and any lower bound |
Record UT_SETTING (one item)
| Field | Type | Default | Meaning |
|---|---|---|---|
minValue |
REAL | −3.4E38 | Lowest value allowed |
maxValue |
REAL | 3.4E38 | Highest value allowed |
above |
INT | 0 | Must be above the value of the item at this position (1 = the first element, whatever the lower bound). 0 = none |
below |
INT | 0 | Must be below the value of the item at this position. 0 = none |
request |
REAL | 0.0 | Written by the HMI or SCADA: the value wanted. Checked when it changes |
cmdCheck |
BOOL | FALSE | Check request again even if unchanged. Set back to FALSE |
value |
REAL | 0.0 | status: the setting in use. Use this one |
refused |
BOOL | status: the last request was refused (until one is accepted) | |
bad |
BOOL | status: value fails the checks now |
|
seen |
REAL | Block memory: the request as last read. Don't write it |
- The checks and
RefusedWhycodes are UT_SETTING_CHECK's. A position outside the array, or
the item's own position, means no check. - Items are checked in array order. When two related items change in the same
scan, the later one is checked against the earlier one's new value; the earlier
one against the later one's old value (it may then needcmdCheck). - Nothing is checked on the first scan after power-up. Declare the array
RETAIN
to keep the settings over a power cut.
(* Levels[1] = L, Levels[2] = H: L.below := 2, H.above := 1 *)
LevelSettings(Items := Levels);
Station.stage[1].stop := Levels[1].value;
Station.stage[1].start := Levels[2].value;
Last updated 2 hours ago