UT_LINEARISE — Lookup table / curve
UT_LINEARISE — Lookup table / curve
Converts a value using a table of points with straight lines between them. Used
for tank strapping tables (level → volume for odd shapes), non-linear sensors,
V-notch weirs and flumes, valve characteristics and pump curves.
Pins
| Pin | Type | Default | What to wire | |
|---|---|---|---|---|
| in | In |
REAL | 0.0 | Value to look up |
| in | Points |
INT | 0 | Use only the first N points (0 = whole array) |
| in | Extrapolate |
BOOL | FALSE | Beyond the ends: FALSE = clamp to the end value, TRUE = extend the end segment |
| out | Out |
REAL | Interpolated result | |
| out | OutOfRange |
BOOL | In beyond the first/last point |
|
| out | TableOk |
BOOL | Table valid (X strictly increasing, all numbers, lengths agree) | |
| out | BadInput |
BOOL | In is NaN or infinite: Out is held |
|
| inout | X |
ARRAY[*] OF REAL | Input points, increasing | |
| inout | Y |
ARRAY[*] OF REAL | Output points |
Declare the arrays once (e.g. ARRAY[1..20] OF REAL) and fill them from your
strapping table. They can be RETAIN so an HMI can edit them; an edit takes
effect on the next scan.
How it works
- Any size and any lower bound:
ARRAY[1..20],ARRAY[0..9],ARRAY[-2..2].
Point 1 is the first element of each array, soXandYmay even start at
different indexes. Points = 0uses the whole arrays, which must then be the same length.
Points = Nuses the first N of each (both must have at least N).- The table is checked every scan. It is not OK if an X is not bigger than
the one before (unsorted or a duplicate), any X or Y is NaN or infinite,
Pointsis negative or longer than an array, or there are no points. Then
TableOkis FALSE andOutandOutOfRangehold their last values. - Exactly on a point gives exactly that point's Y. Y need not increase.
- A one-point table gives its Y everywhere.
- A NaN or infinite
InholdsOutandOutOfRangeand setsBadInput. - The maths runs in LREAL, so tables with values near the REAL limits work.
Extrapolating far beyond a steep end segment can still exceed the REAL range. - Cost: one pass over the points each scan (500 points is fine).
Using it
Strapping(In := LevelM, X := LevelTable, Y := VolumeTable);
VolumeM3 := Strapping.Out;
Last updated 2 hours ago