UT_ALARM — One alarm (ISA-18.2 states)

UT_ALARM — One alarm (ISA-18.2 states)

Turns a condition into a properly managed alarm: on/off delays, acknowledge,
latching, operator shelving, suppress-by-design (Inhibit), out-of-service,
priority and counts. Group alarms with UT_ANNUNCIATOR by
putting their records in an array. The alarm's message is kept in the HMI, by the
alarm's number (its place in the array); the record holds no text.

Pins

Pin Type Default What to wire
in In BOOL FALSE The alarm condition
in Inhibit BOOL FALSE Suppressed by design (e.g. low-flow alarm while the pump is off)
in Ack BOOL FALSE Rising edge: acknowledge
in Clock DT unwired Real-time clock for the time stamps (e.g. UT_SCHEDULE's Data.localTime); unwired = the controller clock (UTC)
out Q BOOL Alarm to annunciate (active, or latched and not yet acknowledged)
out Unacked BOOL Needs acknowledging (flash it)
out Active BOOL Condition present now (after the delays), even while shelved or suppressed
inout Data UT_ALARM_DATA

Record UT_ALARM_DATA

Field Type Default Meaning
onDelay TIME T#0s The condition must last this long to raise the alarm
offDelay TIME T#0s And be gone this long to clear it
latch BOOL FALSE Q stays on until the condition has cleared and it's acknowledged
ackRequired BOOL TRUE FALSE = no acknowledge needed (event / status alarm); latch then has no effect
priority UT_PRIORITY UT_PRIO_MEDIUM
maxShelve TIME T#8h Longest an operator may shelve it. T#0s = shelving not allowed
shelveFor TIME T#0s How long cmdShelve shelves it. T#0s = maxShelve; longer than maxShelve is cut to it
cmdAck BOOL HMI: acknowledge
cmdShelve BOOL HMI: shelve for shelveFor (again while shelved: starts over)
cmdUnshelve BOOL HMI: unshelve now
cmdOutOfService BOOL HMI: out of service
cmdInService BOOL HMI: back in service
cmdResetCount BOOL HMI: count back to 0
state UT_ALARM_STATE Status, see below
active BOOL Status: same as Active
unacked BOOL Status: same as Unacked
shelvedFor TIME Status: shelve time left
count UDINT Status: alarms raised
lastDuration TIME Status: how long the condition lasted last time
sequence UDINT Status: when it was last raised (milliseconds, wraps after 49 days). Orders alarms for the first-out
grpNew BOOL Set when the alarm is raised, cleared by UT_ANNUNCIATOR (so it knows to sound the horn). Don't write it
raisedAt DT Status: when it was last raised (from Clock)
ackedAt DT Status: when it was last acknowledged
clearedAt DT Status: when its condition last cleared

States — UT_ALARM_STATE

State Condition Q Unacked Next
UT_ALM_NORMAL (0) clear condition → UNACKED
UT_ALM_UNACKED present ✔ ✔ ack → ACKED; clears → RTN_UNACKED
UT_ALM_ACKED present ✔ clears → NORMAL
UT_ALM_RTN_UNACKED cleared before ack only if latch ✔ ack → NORMAL; comes back → UNACKED
UT_ALM_SHELVED any expiry or cmdUnshelve
UT_ALM_SUPPRESSED any Inhibit off
UT_ALM_OOS any cmdInService
  • Out of service beats suppressed, suppressed beats shelved.
  • A shelved, suppressed or out-of-service alarm is hidden completely. When it comes back
    with the condition still present it's raised again as a new alarm (counted, needs
    an ack); if the condition has gone it comes back NORMAL.
  • With ackRequired FALSE the alarm goes straight to ACKED; switching ackRequired
    off acknowledges it.
  • When two commands arrive together the alarm stays live: cmdInService beats
    cmdOutOfService, cmdUnshelve beats cmdShelve.
  • A command held on (a Modbus coil left on, a debugger force) acts only once. A command
    written again in the very next scan counts as held.
  • An ack while shelved, suppressed or out of service does nothing.
  • Negative times count as zero.
  • raisedAt, ackedAt and clearedAt are stamped from Clock and each keeps the
    last one (DT#1970-01-01-00:00:00 until the first). Unwired, the controller clock
    is used, which is UTC; wire a local clock for local times.

Power cut

Nothing is kept. After a power-up the alarm is in service and not shelved, count is
0, and an alarm whose condition is still present is raised again.

Using it

LowFlowAlm(In := Flow < 2.0, Inhibit := NOT PumpRunning, Ack := AckPB, Data := Alarms[3]);