# UT_MOTOR_2SPD — Two-speed starter (Dahlander or separate windings)

Low and high speed contactors that are never on together, plus an optional
star-bridge contactor for Dahlander motors, with a changeover dead time and an
optional "start in low first". Modes, interlocks, protection, faults and restart
rules are as [UT_MOTOR](/openplc/utility-blocks/blocks/ut-motor).

## Pins
| | Pin | Type | Default | What to wire |
| --- | --- | --- | --- | --- |
| in | `AutoCmd` | BOOL | FALSE | Run request from your logic (Auto) |
| in | `AutoHigh` | BOOL | FALSE | Speed in Auto: FALSE = low, TRUE = high |
| in | `FeedbackLow` | BOOL | FALSE | Low speed contactor aux |
| in | `FeedbackHigh` | BOOL | FALSE | High speed contactor aux |
| in | `Overload` | BOOL | FALSE | Overload relay tripped (TRUE = tripped; a NC aux through NOT at the pin). Separate windings have two relays: wire them in series / OR them |
| in | `Thermistor` | BOOL | FALSE | PTC relay / thermal switch tripped (a NC contact through NOT at the pin) |
| in | `Current` | REAL | 0.0 | Motor current in amps (used if `fullLoadCurrent` > 0) |
| in | `Interlock` | BOOL | TRUE | FALSE **stops** the motor in every mode |
| in | `Permissive` | BOOL | TRUE | FALSE **blocks starting** only |
| in | `SwHand` / `SwAuto` | BOOL | FALSE | Selector switch (if `modeSource` uses it) |
| in | `LocalStart` | BOOL | FALSE | Local start pushbutton (Hand): starts at the speed chosen last |
| in | `LocalStop` | BOOL | FALSE | Local stop pushbutton (TRUE = pressed; a NC button through NOT at the pin) |
| in | `Reset` | BOOL | FALSE | Reset for MANUAL protections (rising edge) |
| out | `RunLow` | BOOL | | Low speed contactor |
| out | `RunHigh` | BOOL | | High speed contactor (never on with `RunLow`) |
| out | `Bridge` | BOOL | | Dahlander star-bridge contactor: on with `RunHigh` when `dahlander`, never otherwise |
| out | `Running` | BOOL | | Run confirmed by feedback (stays on through a speed change) |
| out | `Fault` | BOOL | | A trip is holding it off |
| out | `Warning` | BOOL | | A protection set to warn is active |
| out | `Ready` | BOOL | | Would start now if asked: healthy, permitted, in Auto or Hand, not waiting out `restartDelay` (stays TRUE while running) |
| out | `Auto` | BOOL | | In Auto mode |
| out | `State` | UT_STATE | | For HMIs |
| out | `HighSpeed` | BOOL | | Running at high speed |
| inout | `Data` | UT_MOTOR_DATA | | Shared motor record ([UT_MOTOR](/openplc/utility-blocks/blocks/ut-motor#record-ut_motor_data-shared-by-every-ut_motor-block)) |
| inout | `Spd` | UT_MOTOR_2SPD_DATA | | The two-speed settings, commands and status (below) |

Always wire the contactors' NC auxiliaries as a hardware interlock as well. The
block never turns both on, but only the wiring stops a welded contactor.

## Record `UT_MOTOR_2SPD_DATA` (pin `Spd`)
| Field | Type | Default | Meaning |
| --- | --- | --- | --- |
| `speedChangeDelay` | TIME | T#1s | Dead time between one speed switching off and the other switching on (both ways) |
| `startInLow` | BOOL | TRUE | A run asked for high starts in low first, then changes up |
| `lowStartTime` | TIME | T#3s | Time in low before that first change up |
| `dahlander` | BOOL | FALSE | Drive the `Bridge` contactor |
| `changeover` | UT_PROTECTION | TRIP · 0 · MANUAL | Contactor feedback wrong for the sequence (`faultCode` bit 9) |
| `cmdLow` / `cmdHigh` | BOOL | FALSE | Hand: run at low / high speed (each acts once, on its rising edge, then cleared: one held TRUE acts once) |
| `highSpeed` (status) | BOOL | | The high speed contactor is on |

A negative `speedChangeDelay` or `lowStartTime` acts as 0 and raises a config warning
(`wrnConfig`). Everything else (modes, protections, `cmdStart` / `cmdStop`, status) is
in the motor record `Data`.

## How it works
- **Speed.** Auto: `AutoHigh`. Hand: `cmdLow` / `cmdHigh` choose the speed and start
  it; `cmdStart` and `LocalStart` start at the speed chosen last. Low and high
  together do nothing. The speed commands are ignored (and cleared) in Off and Auto.
  Switching Auto → Hand keeps the speed it was running at.
- **Start in low:** with `startInLow`, a run asked for high starts in low, stays there
  `lowStartTime`, then changes up through the dead time. Once a run has done that (or
  has been at high), later changes up go straight to high after the dead time.
  Without `startInLow`, high starts directly.
- **Changing speed while running:** the running contactor goes off at once, the dead
  time runs, then the other contactor comes on. The motor stays requested the whole
  time, so `Running` stays on, a permissive does not stop it, and the restart delay
  does not apply. If the request goes back to the old speed during the dead time, that
  contactor comes straight back on.
- **Starting after a stop:** the same speed starts at once; the other speed waits
  until `speedChangeDelay` has passed since the last contactor went off.
- **After a power-up** either speed waits `speedChangeDelay` first, because the motor
  may still be turning.
- **With feedback supervised** (`useFeedback`, not in `simulate`), the new speed also
  waits until the other contactor's aux shows open; with `speedChangeDelay = T#0s`
  there is still at least one scan with both off.
- **Changeover protection** (`changeover`, bit 9, TRIP · MANUAL by default) trips when
  both auxes show closed, when the aux of the speed that is off shows closed while the
  other speed is on, or when a contactor switched off for a speed change still shows
  closed after `stuck.delay` (the other speed is never switched on into it). A contact
  that stays closed at standstill is the welded-contactor protection (`stuck`).
- If the new speed's aux does not confirm after a change, `feedbackLost` trips; if the
  motor never had feedback, `noFeedback` does.

## Status
`statusCode`, `faultId` and `statusText` say the **one main thing** the motor is
doing, or what holds it back, so a technician can see on the HMI why it is not
running without opening the program. A motor asked to run that is not running
always shows a held, fault or configuration status. The most important reason wins:
configuration > fault > held / waiting > warning > running > idle. A warning shows
over "Running" so it is seen. The time that goes with a status is in `timeLeft`.
The text is rebuilt only when the status or the fault changes. The numbers are in
[conventions](/openplc/utility-blocks/conventions#the-numbers).

| `statusCode` | Words | When |
| --- | --- | --- |
| `UT_ST_OFF` | `Off` | Mode Off |
| `UT_ST_IDLE` | `Idle` | Auto with nothing asking it to run |
| `UT_ST_RUN_AUTO` | `Running: Auto` |  |
| `UT_ST_RUN_HAND` | `Running: Hand` | With `handMaxRun`: `timeLeft` is the time left |
| `UT_ST_STARTING` | `Starting` | Run given, run feedback not yet in |
| `UT_ST_STOPPING` | `Stopping` | Stopped, run feedback still on |
| `UT_ST_RUN_GROUP` | `Running: group` | A group ([UT_DUTY](/openplc/utility-blocks/blocks/ut-duty), [UT_PUMP_CASCADE](/openplc/utility-blocks/blocks/ut-pump-cascade)) runs it; `grpRank` is its place |
| `UT_ST_LOW_FIRST` | `Starting: low speed first` | *(this block)* `startInLow`: in low for `lowStartTime` before high; `timeLeft` is the time left |
| `UT_ST_RESTART_DELAY` | `Waiting: restart delay` | Asked to run, `restartDelay` not over yet (`timeLeft` counts down) |
| `UT_ST_INTERLOCK` | `Blocked: interlock` | `Interlock` FALSE (every mode but OOS) |
| `UT_ST_NOT_PERMITTED` | `Not permitted` | `Permissive` FALSE while stopped, in Hand or Auto |
| `UT_ST_HAND_PRESS_START` | `Hand: press start` | Hand and stopped: no start given, or it was dropped (a stop, a trip, the interlock, not permitted) |
| `UT_ST_WAIT_GROUP` | `Waiting: turn in group` | A group owns it and does not run it now |
| `UT_ST_HAND_MAX_RUN` | `Hand: max run, press start` | `handMaxRun` ended the Hand run |
| `UT_ST_MUST_CYCLE` | `Waiting: command must cycle` | After a MANUAL reset, or a local stop in Auto: `AutoCmd` must go off and on |
| `UT_ST_OOS` | `Out of service` |  |
| `UT_ST_DEAD_TIME` | `Waiting: dead time` | *(this block)* Changing speed (or starting at the other speed): both contactors off for `speedChangeDelay`; `timeLeft` counts down |
| `UT_ST_WAIT_OPEN` | `Waiting: contactor to open` | *(this block)* The other speed's contactor aux still shows closed |
| `UT_ST_WARNING` | `Warning: <fault>` | A protection set to WARN is raised, or `Current` is NaN or infinite while a current level is in use (`UT_F_CURRENT_BAD`, `current signal`) |
| `UT_ST_WARN_SETTING` | `Setting: <setting>` | An invalid setting, a safe value in use (settings below) |
| `UT_ST_FAULT` | `Fault: <fault>` | Tripped, AUTO: clears by itself once the cause has gone for `recover` (`timeLeft` while it counts) |
| `UT_ST_FAULT_RETRY` | `Retrying: <fault>` | Tripped, RETRY: the protection's `retries` of `maxRetries` (`timeLeft` while it counts) |
| `UT_ST_FAULT_RESET` | `Latched: <fault>` | Tripped, MANUAL: a reset (pin, `cmdReset`, Off) once the cause has gone |
| `UT_ST_FAULT_LOCKED` | `Locked: <fault>` | RETRY used up: now as MANUAL |
| `UT_ST_CONFIG` | `Config: <setting>` | An invalid setting keeps the motor off |

`<fault>` is `faultId`, one of: `UT_F_OVERLOAD` (overload) · `UT_F_MOTOR_HOT` (motor
too hot) · `UT_F_NO_FEEDBACK` (no run feedback) · `UT_F_FEEDBACK_LOST` (feedback
lost) · `UT_F_WELDED` (contactor welded) · `UT_F_CURRENT_HIGH` (current high) ·
`UT_F_CURRENT_LOW` (current low) · `UT_F_DRIVE` (drive fault) · `UT_F_SPEED_DEV`
(speed deviation) · `UT_F_CHANGEOVER` (changeover) · `UT_F_DRIVE_NOT_READY` (drive
not ready).
`<setting>` is one of: `UT_F_FLC` (full load current) · `UT_F_CURRENT_NEEDS_FLC`
(current needs FLC) · `UT_F_START_MASK` (start mask) · `UT_F_RESTART_DELAY` (restart
delay) · `UT_F_HAND_MAX_RUN` (hand max run) · a protection's name (its `delay`,
`recover` or `maxRetries`).
This block adds the settings `UT_F_SPEED_CHANGE` (speed change delay) · `UT_F_LOW_START_TIME` (low start time), both when negative, and uses `UT_F_CHANGEOVER` for its `changeover` protection.
The rows marked *(this block)* come from its own sequence and show from the scan after it changes.

## Using it
```iecst
Fan1(AutoCmd := Vent.Run, AutoHigh := Vent.Boost, FeedbackLow := K1_Aux, FeedbackHigh := K2_Aux,
     Overload := Fan1_OL, Data := Fan1Data, Spd := Fan1Spd);
K1 := Fan1.RunLow;
K2 := Fan1.RunHigh;
K3 := Fan1.Bridge;
```